“AIR” Series Chillers

Our stand-alone air-cooled chillers, equipped with integrated pump and tank systems, are specifically engineered to efficiently remove heat from the process being cooled and transfer it to the surrounding ambient air. Designed for reliability and performance, these chillers provide consistent temperature control, making them ideal for a wide range of industrial and commercial applications where efficient heat dissipation is essential.

Available 1/3 to 1000 Tons

Our air-cooled chillers are available in sizes from 1/3 Ton to 1000 Tons, including options for central chillers, to meet any cooling demand.

Multiple Air-Cooled Chiller Configurations Available

Models available for indoor, outdoor, and split systems. Our engineering team has the expertise and experience to design air-cooled chiller systems that fit your application and needs. 

Model Capacity Piping Dimensions Pump Rated Load Amps Dry Weight
"AIR" Series BTUs/hr Inlet Outlet Length Width Height GPM PSI 230/1 460/3 U.S. Pounds
AIR 03004,0001/2"1/2"25"16"29"450115V180
AIR 05006,0001/2"1/2"25"16"29"45010205
AIR 100012,0001/2"1/2"25"34"34"45014250
AIR 150018,0001/2"1/2"25"34"34"45018300
AIR 200024,0003/4"3/4"38"34"38"102822390
AIR 300036,0001-1/4"1-1/4"50"34"67"18389750
AIR 500060,0001-1/4"1-1/4"50"34"67"183811795
AIR 750090,0001-1/4"1-1/4"70"42"67"383817925
AIR 10,000120,0001-1/4"1-1/4"70"42"67"383823950
AIR 12,000144,0001-1/4"1-1/4"42"92"70"3838281200
AIR 15,000180,0001-1/4"1-1/4"92"42"70"3838311290
AIR 20,000240,0002"2"97"56"89"7045391870
AIR 25,000300,0002"2"97"56"89"7045522050
AIR 30,000350,0002"2"97"56"89"7045572190
AIR 35,000420,0002"2"97"56"89"7045652290
AIR 40,000-DC488,0003"3"136"100"101"14045783600
AIR 50,000–DC600,0003"3"136"100"101"14045943800
AIR 60,000–DC720,0003"3"136"100"101"140451154090
AIR 70,000–DC840,0003"3"136"100"101"140451394275
AIR 90,000–3CT1,080,000 “AIR” Models are available in capacities up to 12,000,000+ BTUs/hr

Please contact factory for additional information, specifications, and dimensions.
AIR 105,000–4CT1,260,000
AIR 120,000–4CT1,440,000
AIR 140,000–4CT1,680,000
AIR 180,000–6CT2,160,000
AIR 210,000–6CT2,520,000

Frequently Asked Questions About Our Air Series Chillers

Q: What capacity range do the AIR Series chillers cover?
The AIR Series is available from 1/3 ton up to 1,000 tons, with central-plant configurations reaching 12,000,000+ BTU/hr. Sizing is matched to your process heat load, flow rate, and required leaving-fluid temperature.
Q: Do air-cooled chillers require a separate pump and reservoir?
No. Every AIR Series unit ships with an integrated pump and tank, so it arrives as a self-contained package. That reduces installation labor and the number of third-party components you have to specify and source.
Q: Can the AIR Series be installed outdoors?
Yes. Indoor, outdoor, and split configurations are available, and outdoor units can be built with low-ambient packages for cold-climate operation. Provide your site’s ambient temperature range so the condenser and controls are rated correctly.
Q: What electrical supply do these chillers require?
Depending on capacity, AIR Series units run on 115V single-phase, 230V single-phase, or 460V three-phase power. Rated-load amps are listed per model so your electrical contractor can size circuits before delivery.
Q: When is an air-cooled chiller the right choice over water-cooled?
Air-cooled units are preferred when you want to avoid the cost, water usage, and maintenance of a cooling tower or water loop. They suit moderate ambients and sites where water is scarce or expensive, though water-cooled units can be more efficient in high-ambient environments.